Ground Transient
Terminator (GTT), Test and Evaluation
The following captures are from 1 kHz to 1MHz at
decade intervals. The attenuation is apparent as the frequency is increased.

Attenuation @ 1 KHz

Attenuation @ 10 KHz

Attenuation @ 100 KHz

Attenuation @ 1 MHz
Calculated attenuation
across pre-established test frequency range

The
following captures show the effective transient response
time for the GTT. The final graph detail the peak (x50).
The test was conducted using a high-level transient
signal, simulated using a 900uF capacitor bank charged
to 165 volts DC and then switched onto a 7.5 ohm load.
The duration of the pulse was nominally 20ms
corresponding to a power transient of approximately
600W.
Without GTT Technology

With GTT Technology

Comparative Transient response

|